Siemens G130 List Manual page 270

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0828[0...n]
BI: Motor changeover feedback signal / Mot_chng fdbk sig
VECTOR_G
Can be changed: C2(3), T
Data type: Unsigned32 / Binary
P-Group: Motor
Not for motor type: -
Min
-
Description:
Sets the signal source for the feedback signal when changing over the motor.
For p0833.0 = 1 the following applies:
This feedback signal (0/1 edge) is required after a motor changeover to enable the pulses.
Dependency:
Refer to: p0833
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
r0830.0...15
CO/BO: Motor changeover status word / Mot_chngov ZSW
VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays the status word of the motor changeover.
These signals can be connected to digital outputs to change over the motor.
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Dependency:
Refer to: p0827
p0831[0...15]
BI: Motor changeover contactor feedback / Mot_chg cont fdbk
VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Motor
Not for motor type: -
Min
-
Description:
Sets the signal source for the feedback signal of the contactors when changing over motors.
There is a fixed inter-relationship between energizing the contactor and the feedback signal.
Example:
A changeover is to be made between MDS0 (motor 0) and MDS1 (motor 1). The contactors should be switched using
bit 4 (contactor 0) and 5 (contactor 1). The changeover should be made with an interconnection of the feedback
signal.
270
Signal name
Motor selection bit 0
Motor selection bit 1
Motor selection bit 2
Motor selection bit 3
Motor selection bit 4
Motor selection bit 5
Motor selection bit 6
Motor selection bit 7
Motor selection bit 8
Motor selection bit 9
Motor selection bit 10
Motor selection bit 11
Motor selection bit 12
Motor selection bit 13
Motor selection bit 14
Motor selection bit 15
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
High
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 8575
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8575
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Access level: 3
Func. diagram: 8575
Unit selection: -
Expert list: 1
Factory setting
0