p1628[0...n]
Current model controller dynamic factor / I_mod_ctr dyn_fact
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: ASM, PMSM, REL
Min
1 [%]
Description:
Sets the dynamic response factor for the current model controller.
p1629[0...n]
Current model controller P gain / I_mod_ctrl Kp
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: ASM, PMSM, REL
Min
0.000
Description:
Sets the proportional gain for the current model controller.
This value is automatically pre-set using p3900 or p0340 when commissioning has been completed.
p1630[0...n]
Current model controller integral time / I_mod_ctrl Tn
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: ASM, PMSM, REL
Min
0.00 [ms]
Description:
Sets the integral time for the current model controller.
This value is automatically pre-set using p3900 or p0340 when commissioning has been completed.
r1631
Current model controller P gain effective / I_mod ctrl Kp eff
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: ASM, PMSM, REL
Min
-
Description:
Displays the effective P gain of the current model controller.
r1632
Current model controller integral time effective / I_mod_ctrl Tn eff
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: ASM, PMSM, REL
Min
- [ms]
Description:
Displays the effective integral time of the current model controller.
430
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
400 [%]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100000.000
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000.00 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [ms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 6727
Unit selection: -
Expert list: 1
Factory setting
50 [%]
Access level: 4
Func. diagram: 6727
Unit selection: -
Expert list: 1
Factory setting
0.000
Access level: 4
Func. diagram: 6727
Unit selection: -
Expert list: 1
Factory setting
0.00 [ms]
Access level: 3
Func. diagram: 6727
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 6727
Unit selection: -
Expert list: 1
Factory setting
- [ms]