[0] = T0
[1] = T1
[2] = T2
Note:
Limiting on:
If signals are output outside the permissible measuring range, the signal is limited to 4.98 V or to 0 V.
Limiting off:
If signals are output outside the permissible measuring range, this causes signal overflow. In the case of signal
overflow, the signal jumps from 0 V to 4.98 V or from 4.98 V to 0 V.
r0786[0...2]
Test socket scaling per volt / TestSktScale/Volt
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Terminals
CU_G150_DP
Not for motor type: -
Min
-
Description:
Displays the scaling of the signal to be output.
A change in the output voltage by 1 volt corresponds to the value in this parameter. The units are determined by the
interconnected test signal.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Refer to: p0771, r0772, r0774, p0777, p0778, p0779, p0780, p0783, p0784
Note:
Example:
r0786[0] = 1500.0 and the measuring signal is r0063 (CO: Actual speed smoothed [rpm]).
A change of 1 V at the output of test socket T0 corresponds to 1500.0 [rpm].
p0788[0...2]
Test sockets physical address / Test skt PhyAddr
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32
CU_G130_DP,
P-Group: Terminals
CU_G150_DP
Not for motor type: -
Min
0000 bin
Description:
Sets the physical address to output signals via the test sockets.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Changes only become effective if p0776 does not equal 99.
Refer to: p0789, r0790
p0789[0...2]
Test sockets physical address gain / TestSktPhyAddrGain
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Terminals
CU_G150_DP
Not for motor type: -
Min
-340.28235E36
Description:
Sets the gain of a signal output of a physical address via test sockets.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Changes only become effective if p0776 does not equal 99.
Refer to: p0788
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1111 1111 1111 1111 1111 1111
1111 1111 bin
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
340.28235E36
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8134
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 bin
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.00000
263

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents