2 Parameters
2.2 List of parameters
p0389[0...n]
Excitation rated no-load current / Exc I_noload_rated
VECTOR_G
Can be changed: C2(1, 3)
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, PMSM, REL,
RESM
Min
0.00 [A]
Description:
Sets the rated no-load current (I_F0) for the excitation.
p0390[0...n]
Rated excitation current / Exc I_rated
VECTOR_G
Can be changed: C2(1, 3)
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, PMSM, REL,
RESM
Min
0.00 [A]
Description:
Setting the rated current (I_F) of the controlled excitation rectifier (DC master).
p0391[0...n]
Current controller adaptation starting point Kp / I_adapt pt Kp
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL
Min
0.00 [Arms]
Description:
Sets the starting point of the current-dependent current controller adaptation where the current controller gain p1715
is effective.
Dependency:
Refer to: p0392, p0393, p1402, p1715
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0392[0...n]
Current controller adaptation starting point Kp adapted / I_adapt pt Kp adap
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL
Min
0.00 [Arms]
Description:
Sets the starting point of the current-dependent current controller adaptation where the adapted current controller
gain p1715 x p0393 is effective.
Dependency:
Refer to: p0391, p0393, p1402, p1715
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
158
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
10000.00 [A]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
10000.00 [A]
Calculated: CALC_MOD_REG
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
6000.00 [Arms]
Calculated: CALC_MOD_REG
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
6000.00 [Arms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: 6727
Unit selection: -
Expert list: 1
Factory setting
0.00 [A]
Access level: 1
Func. diagram: 6727
Unit selection: -
Expert list: 1
Factory setting
0.00 [A]
Access level: 3
Func. diagram: 6714
Unit selection: -
Expert list: 1
Factory setting
0.00 [Arms]
Access level: 3
Func. diagram: 6714
Unit selection: -
Expert list: 1
Factory setting
0.00 [Arms]