2 Parameters
2.2 List of parameters
p0145[0...n]
Activate/deactivate encoder interface / Enc_intf act/deact
VECTOR_G, ENC
Can be changed: C1(4), U, T
Data type: Integer16
P-Group: Data sets
Not for motor type: -
Min
0
Description:
Setting to activate/deactivate an encoder interface (Sensor Module).
Value:
0:
1:
2:
Recommendation:
After inserting a component, before activating, first wait for Alarm A01317.
Dependency:
Refer to: r0146
Refer to: A01314, A01317
Note:
The deactivation of an encoder interface corresponds to the"parking encoder" function and has the same effect.
The activation of a component can be rejected if the component was inserted for the first time.
In this case, it is only possible to activate the component when the pulses for all of the drive objects are inhibited.
With the encoder interface for encoder 1 (motor encoder), the relevant drive object for writing the parameter must be
in the "Ready for operation" state.
With the encoder interface for encoders 2 and 3, the parameter can also be written during operation.
For value = 0, 2:
When a component is deactivated it no longer outputs any errors.
If value = 0:
The component was completely commissioned and is deactivated using this value. It can be removed from the
DRIVE-CLiQ without any error.
If value = 1:
The component must be available for error-free operation.
If value = 2:
A component in a project generated offline and set to this value must never be inserted in the actual topology from
the very start.
For components that comprise several individual components (e.g. Double Motor Modules), it is not permissible to
set just one subset to this value.
r0146[0...n]
Encoder interface active/inactive / Enc_intf act/inact
VECTOR_G, ENC
Can be changed: -
Data type: Integer16
P-Group: Data sets
Not for motor type: -
Min
0
Description:
Displays the "active" or "inactive" state of an encoder interface (Sensor Module).
Value:
0:
1:
Dependency:
Refer to: p0105, p0145, p0480, p0897
r0147[0...n]
Sensor Module EEPROM data version / SM EEPROM version
VECTOR_G, ENC
Can be changed: -
Data type: Unsigned32
P-Group: Encoder
Not for motor type: -
Min
-
Description:
Displays the version of the EEPROM data of the Sensor Module.
Dependency:
Refer to: r0127, r0157
96
Deactivate component
Activate component
Component deactivate and not present
Component inactive
Component active
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents