r4101
TM31 sensor resistance / TM31 R_sensor
TM31
Can be changed: -
Data type: Unsigned16
P-Group: Terminals
Not for motor type: -
Min
- [ohm]
Description:
Displays the actual resistance value of the temperature sensor connected at the Terminal Module.
Note:
The maximum measurable resistance value is approx. 1720 Ohm.
The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
p4102[0...7]
TM120 fault threshold/alarm threshold / TM120 F/A_thresh
TM120
Can be changed: U, T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
-48 [°C]
Description:
Sets the fault threshold/alarm threshold for Terminal Module 120 (TM120).
A35211 is initiated, if the temperature actual value r4105[0] > p4102[0]
F35207 is initiated if the temperature actual value r4105[0] > p4102[1] or timer p4103[0] has expired
A35212 is initiated, if the temperature actual value r4105[1] > p4102[2]
F35208 is initiated if the temperature actual value r4105[1] > p4102[3] or timer p4103[1] has expired
A35213 is initiated, if the temperature actual value r4105[2] > p4102[4]
F35209 is initiated if the temperature actual value r4105[2] > p4102[5] or timer p4103[2] has expired
A35214 is initiated, if the temperature actual value r4105[3] > p4102[6]
F35210 is initiated if the temperature actual value r4105[3] > p4102[7] or timer p4103[3] has expired
For alarms A35211, A35212, A35213, A35214 the following applies:
- Remains until the temperature actual value (r4105[0...3]) reaches or falls below the value (p4102[0, 2, 4, 6] -
hysteresis).
For fault F35207, F35208, F35209, F35210 the following applies:
- Remains until the temperature actual value (r4105[0...3]) reaches or falls below the value (p4102[1, 3, 5, 7] -
hysteresis) and the fault has been acknowledged.
- the hysteresis value is 5 K and cannot be changed.
Index:
[0] = Channel 0 alarm threshold (A35211)
[1] = Channel 0 fault threshold (F35207)
[2] = Channel 1 alarm threshold (A35212)
[3] = Channel 1 fault threshold (F35208)
[4] = Channel 2 alarm threshold (A35213)
[5] = Channel 2 fault threshold (F35209)
[6] = Channel 3 alarm threshold (A35214)
[7] = Channel 3 fault threshold (F35210)
Dependency:
Refer to: p4103
Notice:
Fault F35207 ... F35210 only causes the drive to shut down if there is at least one BICO interconnection between the
drive and TM120.
For p4102[0...7] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" (p4100[0...3] = 1), the following applies:
To activate the corresponding alarm or fault, p4102[0...7] must be set <= 250 °C.
Note:
The temperature sensor is connected to the following terminals:
X521.2(+) and X521.1(-) = channel 0
X521.4(+) and X521.3(-) = channel 1
X521.6(+) and X521.5(-) = channel 2
X521.8(+) and X521.7(-) = channel 3
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [ohm]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
251 [°C]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 9576
Unit selection: -
Expert list: 1
Factory setting
- [ohm]
Access level: 1
Func. diagram: 9605, 9606
Unit selection: -
Expert list: 1
Factory setting
251 [°C]
669