p0864
BI: Infeed operation / INF operation
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the operating signal of the infeed (e.g. BO: r0863.0).
Dependency:
Refer to: r0863
Note:
The sequence control of a servo/vector drive requires this signal.
The following applies for an infeed without DRIVE-CLiQ:
For these infeeds, the "ready" message is available via an output terminal. This signal must be connected to a digital
input. The drives supplied from this infeed must use this signal as ready signal (BI: p0864 = digital input).
p0867
Power unit main contactor holding time after OFF1 / PU t_MC after OFF1
VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
0.0 [ms]
Description:
Sets the main contactor holding time after OFF1
After withdrawing the OFF1 enable (signal source of p0840), the main contactor is only opened after the main
contactor holding time has elapsed.
Recommendation:
When operating a drive connected to SINUMERIK, which only closes the main contactor with the OFF1 command
(blocksize, chassis), p0867 should be set as a minimum to 50 ms.
Dependency:
Refer to: p0869
Note:
For p0869 = 1 (keep main contactor closed for STO), after withdrawing STO, the switching-on inhibited must be
acknowledged via the signal source of p0840 = 0 (OFF1) – and before the main contactor holding time expires,
should go back to 1, otherwise the main contactor will open.
p0868
Power unit debounce time/wait time / PU t_debounce/t_w
VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
0 [ms]
Description:
For Motor Modules, "Chassis" format:
Setting the debounce time for the DC circuit breaker
For AC/AC converters, "Chassis" format:
Setting the wait time for the thyristor rectifier.
Note:
The following applies if p0868 = 65000 ms:
The debounce time defined internally in the power unit's EEPROM is implemented.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
500.0 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65000 [ms]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 2610, 8710,
8910
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
50.0 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
65000 [ms]
283