Siemens G130 List Manual page 643

Hide thumbs Also See for G130:
Table of Contents

Advertisement

Dependency:
Refer to: r4022
Note:
DI: Digital Input
p4028
TM31 set input or output / TM31 DI or DO
TM31
Can be changed: T
Data type: Unsigned32
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the bidirectional digital inputs/outputs as input or output on the Terminal Module 31 (TM31).
Bit field:
Bit
08
09
10
11
Note:
DI/DO: Bidirectional Digital Input/Output
p4030
BI: TM31 signal source for terminal DO 0 / TM31 s_src DO 0
TM31
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the digital output DO 0 (X542.1, X542.2, X542.3) of Terminal Module 31 (TM31).
Digital output 0 of TM31 is a relay output.
If the signal at the binector input p4030 is low, then terminal COM 0 (X542.2) is connected to NC 0 (X542.1). This
connection also matches the mechanical quiescent setting of the relay.
If the signal at the binector input p4030 is high, then terminal COM 0 (X542.2) is connected to NO 0 (X542.3).
Note:
DO: Digital Output
NC: Normally Closed contact
NO: Normally Open contact
p4030
BI: TB30 signal source for terminal DO 0 / TB30 s_src DO 0
TB30
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for digital output DO 0 (X481.5) of the Terminal Board 30 (TB30).
Note:
DO: Digital Output
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
DI/DO 8 (X541.2)
DI/DO 9 (X541.3)
DI/DO 10 (X541.4)
DI/DO 11 (X541.5)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Output
Output
Output
Output
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 9549, 9560,
9562
Unit selection: -
Expert list: 1
Factory setting
0000 0000 0000 0000 bin
0 signal
Input
Input
Input
Input
Access level: 1
Func. diagram: 9549, 9556
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 9099, 9102
Unit selection: -
Expert list: 1
Factory setting
0
FP
-
-
-
-
643

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents