Siemens G130 List Manual page 257

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p0738
BI: CU signal source for terminal DI/DO 8 / CU S_src DI/DO 8
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32 / Binary
CU_G130_DP,
P-Group: Commands
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 8 (X122.9 / X121.7).
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.8 = 1).
DI/DO: Bidirectional Digital Input/Output
p0739
BI: CU signal source for terminal DI/DO 9 / CU S_src DI/DO 9
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32 / Binary
CU_G130_DP,
P-Group: Commands
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 9 (X122.10 / X121.8).
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.9 = 1).
DI/DO: Bidirectional Digital Input/Output
p0740
BI: CU signal source for terminal DI/DO 10 / CU S_src DI/DO 10
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32 / Binary
CU_G130_DP,
P-Group: Commands
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 10 (X122.12 / X121.10).
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.10 = 1).
DI/DO: Bidirectional Digital Input/Output
p0741
BI: CU signal source for terminal DI/DO 11 / CU S_src DI/DO 11
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32 / Binary
CU_G130_DP,
P-Group: Commands
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 11 (X122.13 / X121.11).
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 2119, 2130
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 2130
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 2131
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 2119, 2131
Unit selection: -
Expert list: 1
Factory setting
0
257

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents