For index [2]:
Sets the pretrigger time, [ms].
This time is included in the recording time and cannot be longer than the recording time p6999[1].
Note:
- when the recording time is automatically reduced, the pretrigger time is correspondingly reduced as well.
- the pretrigger time that can be realized is displayed in r6991[2].
For index [3]:
Enables or disables the output of message A49998 when the trigger event is triggered.
For index [4]:
p6999[4] = n, n = 0 ... 4
Recording with the factor, which extends the record time p6999[1] and the pre-trigger time p6999[2] 2^n times, and
reduces the number of signals 2^n times.
Example:
Number of drive objects = 1, p0115[0] = 250 µs, p6999[1] = 2000, p6999[2] = 1000, p6999[4] = 4
--> recording time: 2000 ms * 2^4 = 32 s, pre-trigger time:1000 ms * 2^4 = 16 s, number of signals 64/16 = 4.
When setting p6999[4] to 0, the results are as follows:
--> recording time: 2000 ms, pre-trigger time: 1000 ms, number of signals: 64
r7000
CO: Par_circuit No. of active power units / Qty active PU
VECTOR_G (Parallel),
Can be changed: -
B_INF (Parallel)
Data type: Unsigned16
P-Group: Modulation
Not for motor type: -
Min
-
Description:
Displays the active power units for a parallel circuit configuration.
Dependency:
Refer to: p7001
p7001[0...n]
Par_circuit power units enable / PU enable
VECTOR_G (Parallel),
Can be changed: T
B_INF (Parallel)
Data type: Integer16
P-Group: Modulation
Not for motor type: -
Min
0
Description:
Setting to enable the power units for a parallel connection.
Value:
0:
1:
Dependency:
Refer to: r7000
Caution:
For a parallel connection, the following applies:
When deactivating individual power units using this parameter, it is not permissible that the power units of the parallel
connection involved are connected. Infeed units should be disconnected from the line supply (for example, using a
contactor). Motor feeder cables should be disconnected. In addition, defective power units should be disconnected
from the DC link.
Note:
For motors with separate winding systems (p7003 = 1) it is not possible to inhibit an individual power unit.
p7001 is automatically reset if a power unit is deactivated via p0125 or p0895.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Deactivated
Activated
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
751