p0393[0...n]
Current controller adaptation P gain scaling / I_adapt Kp scal
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL
Min
0.00 [%]
Description:
Sets the factor for the current controller P gain in the adaptation range (e.g. r0078 > p0392, if p0392 > p0391).
The value is referred to p1715.
Dependency:
Refer to: p0391, p0392, p1402, p1715
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
For p0393 = 100 % or p1402.2 = 0, the current controller adaptation is disabled and p1715 is effective over the entire
range.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
r0395[0...n]
Actual stator resistance / R_stator act
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
- [ohm]
Description:
Displays the actual stator resistance (phase value).
The parameter value also contains the temperature-independent cable resistance.
Dependency:
In the case of induction motors the parameter is also affected by the motor temperature model.
Refer to: p0350, p0352, p0620
Note:
In each case, only the stator resistance of the active Motor Data Set is included with the stator temperature of the
thermal motor model.
r0396[0...n]
Actual rotor resistance / R_rotor act
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PMSM, SESM, REL,
RESM
Min
- [ohm]
Description:
Displays the actual rotor/secondary section resistance (phase value).
The parameter is affected by the motor temperature model.
Dependency:
Refer to: p0354, p0620
Note:
In each case, only the rotor resistance of the active Motor Data Set is included with the rotor temperature of the
thermal motor model.
This parameter is not used for synchronous motors (p0300 = 2xx).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: CALC_MOD_REG
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
1000.00 [%]
Calculated: -
Dyn. index: MDS, p0130
Unit group: 16_1
Scaling: -
Max
- [ohm]
Calculated: -
Dyn. index: MDS, p0130
Unit group: 16_1
Scaling: -
Max
- [ohm]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6714
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 3
Func. diagram: 6301, 6730,
6731, 6732
Unit selection: p0349
Expert list: 1
Factory setting
- [ohm]
Access level: 3
Func. diagram: 6730
Unit selection: p0349
Expert list: 1
Factory setting
- [ohm]
159