2 Parameters
2.2 List of parameters
p9904
Topology comparison acknowledge differences / Topo_compare ackn
CU_G130_PN,
Can be changed: C1(1)
CU_G150_PN,
Data type: Unsigned32
CU_G130_DP,
P-Group: Topology
CU_G150_DP
Not for motor type: -
Min
0000 hex
Description:
If, when comparing the actual topology and target topology, only error has occurred, that can be acknowledged, then
using this parameter, a new comparison can be started - acknowledging the error in the target topology.
Differences that can be acknowledged:
- topology comparison, component shifted
- topology comparison, serial number of a component has been detected to be different (byte 3 = 1)
- topology comparison shows one component that is connected differently
The following parameter values are available:
p9904 = 1 --> the procedure is started.
p9904 = 0 after starting --> the procedure has been successfully completed.
p9904 = 1 after starting --> the procedure has not been successfully completed.
The possible causes for an unsuccessful procedure are located in bytes 4, 3, 2.
Byte 2:
Number of structural differences.
Byte 3:
Number of differences that can be acknowledged (p9904).
Byte 4:
Number of differences. These differences can be resolved as follows:
- sets the topology comparison (p9906 or p9907/p9908).
- change over the actual topology.
The appropriate action should be selected corresponding to the message that is displayed/output.
Note:
In order to permanently accept the acknowledgment of the fault that can be resolved, then it must be saved in a non-
volatile fashion (p0977).
p9905
Device specialization / Specialization
CU_G130_PN,
Can be changed: C1(1)
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
P-Group: Topology
CU_G150_DP
Not for motor type: -
Min
0
Description:
With p9905 = 1, the serial numbers and the hardware versions of all of the components are transferred from the
actual topology into the target topology and a new comparison is started.
For this device specialization, the components of the target topology may only differ from those of the actual topology
by the serial numbers.
With p9905 = 2, the serial numbers, the hardware versions and the article numbers of all of the components are
transferred from the actual topology into the target topology and a new comparison is started.
For this device specialization, the components of the target topology may only differ from those of the actual topology
by the serial numbers and article numbers.
Note:
p9905 is automatically set to 0 at the end of the operation.
In order to permanently accept the data, it is necessary to save in a non-volatile fashion (p0977).
1014
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
FFFF FFFF hex
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 hex
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0