2 Parameters
2.2 List of parameters
r1343
CO: I_max controller frequency output / I_max_ctrl f_outp
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
- [rpm]
Description:
Displays the effective frequency limit.
Dependency:
Refer to: p1340
r1344
I_max controller voltage output / I_max_ctrl U_outp
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
- [Vrms]
Description:
Displays the amount by which the converter output voltage is reduced.
Dependency:
Refer to: p1340
p1345[0...n]
I_max voltage controller proportional gain / I_max_U_ctrl Kp
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
0.000
Description:
Sets the proportional gain for the I_max voltage controller.
Dependency:
Refer to: p1340
Note:
The controller settings are also used in the current controller of the DC braking (refer to p1232).
p1346[0...n]
I_max voltage controller integral time / I_max_U_ctrl Tn
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
0.000 [s]
Description:
Sets the integral time for the I_max voltage controller.
Dependency:
Refer to: p1340
Note:
The controller settings are also used in the current controller of the DC braking (refer to p1232).
For p1346 = 0, the following applies:
The integral time of the I_max voltage controller is deactivated.
380
Calculated: -
Dyn. index: -
Unit group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: -
Unit group: 5_1
Scaling: p2001
Max
- [Vrms]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100000.000
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
50.000 [s]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 6300
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 3
Func. diagram: 6300
Unit selection: p0505
Expert list: 1
Factory setting
- [Vrms]
Access level: 3
Func. diagram: 6300, 7017
Unit selection: -
Expert list: 1
Factory setting
0.000
Access level: 3
Func. diagram: 6300, 7017
Unit selection: -
Expert list: 1
Factory setting
0.030 [s]