Siemens G130 List Manual page 381

Hide thumbs Also See for G130:
Table of Contents

Advertisement

r1348
CO: U/f control Eco factor actual value / Uf Eco fac act v
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
- [%]
Description:
Displays the economic factor determined for optimizing motor consumption.
Dependency:
Refer to: p1335
Note:
The value is only determined for operating modes with Economic (p1300 = 4, 7).
p1349[0...n]
U/f mode resonance damping maximum frequency / Uf res_damp f_max
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
0.00 [Hz]
Description:
Sets the maximum output frequency for resonance damping for U/f control.
Resonance damping is inactive above this output frequency.
Dependency:
Refer to: p1338, p1339
Note:
For p1349 = 0, the changeover limit is automatically set to 95 % of the rated motor frequency - however, to a max. of
45 Hz.
p1350[0...n]
U/f control soft start / U/f soft start
VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: V/f open-loop control
Not for motor type: -
Min
0
Description:
Sets whether the voltage is continuously increased during the magnetizing phase (p1350 = 1, On) or whether it jumps
directly to the voltage boost (p1350 = 0, Off).
Value:
0:
1:
Dependency:
The function is not effective for p1300 = 15.
Note:
The settings for this parameter have the following advantages and disadvantages:
0 = off (jump directly to voltage boost)
Advantage: Flux is established quickly -> torque is quickly available
Disadvantage: The motor can move while it is being magnetized
1 = on (voltage is continually established)
Advantage: The motor is unlikely to rotate
Disadvantage: The flux is established slower -> torque is available later
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
OFF
ON
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [%]
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
3000.00 [Hz]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: 6300, 6301
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 6310
Unit selection: -
Expert list: 1
Factory setting
0.00 [Hz]
Access level: 3
Func. diagram: 6300
Unit selection: -
Expert list: 1
Factory setting
0
381

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents