2 Parameters
2.2 List of parameters
p4816
Function generator output signal integer number scaling / FG outp integ scal
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer32
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
-2147483648
Description:
Sets the scaling for the integer number of the output signal for the function generator.
Dependency:
Refer to: r4805, r4817
Note:
The parameter can only be changed in the following operating states:
r4805 = 0, 4, 6
r4817
CO: Function generator output signal integer number / FG outp integ no.
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Integer32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
-
Description:
Display and connector output for the integer number of the output signal for the function generator.
Dependency:
Refer to: p4816
Note:
The value is output independent of the function generator operating mode.
r4818
CO: Function generator output signal / FG outp_sig
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
- [%]
Description:
Displays the output signal for the function generator.
Dependency:
Refer to: p4810
Note:
The value is displayed independently of the function generator mode.
p4819
BI: Function generator control / FG control
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32 / Binary
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the signal source to control the function generator.
When the function generator is running, signal generation is stopped with a 0 signal from BI: p4819 and p4800 is set
to 0.
Dependency:
Refer to: p4800
724
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2147483647
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
- [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
1