p2190[0...n]
Load monitoring torque threshold 3 lower / M_thresh 3 lower
VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [Nm]
Description:
Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency:
The following applies: p2190 < p2189
Refer to: p2184, p2189
Refer to: A07926
Note:
The lower envelope curve is defined by p2186, p2188 and p2190.
p2192[0...n]
Load monitoring delay time / Load monit t_del
VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [s]
Description:
Sets the delay time to evaluate the load monitoring.
p2194[0...n]
Torque threshold value 2 / M_thresh val 2
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [%]
Description:
Sets the torque threshold value for the message "Torque utilization < torque threshold value 2" (BO: r2199.11).
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency:
Refer to: r0033, p2195, r2199
p2195[0...n]
Torque utilization switch-off delay / M_util t_off
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.0 [ms]
Description:
Sets the switch-off delay time for the negated signal "run-up completed".
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency:
Refer to: p2174, p2194
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: DDS, p0180
Unit group: 7_1
Scaling: -
Max
20000000.00 [Nm]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
65.00 [s]
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1000.0 [ms]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8013
Unit selection: p0505
Expert list: 1
Factory setting
0.00 [Nm]
Access level: 3
Func. diagram: 8013
Unit selection: -
Expert list: 1
Factory setting
10.00 [s]
Access level: 2
Func. diagram: 8012
Unit selection: -
Expert list: 1
Factory setting
90.00 [%]
Access level: 2
Func. diagram: 8012
Unit selection: -
Expert list: 1
Factory setting
800.0 [ms]
559