Siemens G130 List Manual page 293

Hide thumbs Also See for G130:
Table of Contents

Advertisement

r0945[8], r0949[8], r0948[8], r2109[8], r3115[8] --> 1st acknowledged fault case, fault 1
. . .
r0945[15], r0949[15], r0948[15], r2109[15], r3115[15] --> 1st acknowledged fault case, fault 8
. . .
r0945[56], r0949[56], r0948[56], r2109[56], r3115[56] --> 7th acknowledged fault case, fault 1
. . .
r0945[63], r0949[63], r0948[63], r2109[63], r3115[63] --> 7th acknowledged fault case, fault 8
r0946[0...65534]
Fault code list / Fault code list
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Lists the fault codes stored in the drive unit.
The indices can only be accessed with a valid fault code.
Dependency:
The parameter assigned to the fault code is entered in r0951 under the same index.
r0947[0...63]
Fault number / Fault number
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
This parameter is identical to r0945.
r0948[0...63]
Fault time received in milliseconds / t_fault recv ms
All objects
Can be changed: -
Data type: Unsigned32
P-Group: Messages
Not for motor type: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the fault occurred.
Dependency:
Refer to: r0945, r0947, r0949, r2109, r2114, r2130, r2133, r2136, r3115, r3120, r3122
Notice:
The time comprises r2130 (days) and r0948 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
r0949[0...63]
Fault value / Fault value
All objects
Can be changed: -
Data type: Integer32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays additional information about the fault that occurred (as integer number).
Dependency:
Refer to: r0945, r0947, r0948, r2109, r2130, r2133, r2136, r3115, r3120, r3122
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8060
Unit selection: -
Expert list: 0
Factory setting
-
Access level: 3
Func. diagram: 8050, 8060
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8050, 8060
Unit selection: -
Expert list: 1
Factory setting
- [ms]
Access level: 3
Func. diagram: 8050, 8060
Unit selection: -
Expert list: 1
Factory setting
-
293

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents