Siemens G130 List Manual page 113

Hide thumbs Also See for G130:
Table of Contents

Advertisement

Dependency:
Refer to: p0205
r0207[0...4]
Rated power unit current / PU PI_rated
B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [Arms]
Description:
Displays the rated power unit power for various load duty cycles.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 cont duty cyc
[4] = S6 load duty cycle
Dependency:
Refer to: p0205
Note:
The following applies for booksize power units:
The display value corresponds to the rated DC link current at 600 V (according to the SINAMICS S120 Manual).
For chassis power units, the following applies:
The display value corresponds to the rated input current at the rated line voltage (according to the SINAMICS S120
Manual).
r0208
Rated power unit line supply voltage / PU U_rated
VECTOR_G, B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [Vrms]
Description:
Displays the rated line supply voltage of the power unit.
r0208 = 400: 380 - 480 V +/-10 %
r0208 = 500: 500 - 600 V +/-10 %
r0208 = 690: 660 - 690 V +/-10 %
For the Basic Line Module (BLM) the following applies:
r0208 = 690: 500 - 690 V +/-10 %
r0209[0...4]
Power unit maximum current / PU I_max
VECTOR_G, B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [Arms]
Description:
Displays the maximum output current of the power unit.
Index:
[0] = Catalog
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency:
Refer to: p0205
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [Arms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [Vrms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [Arms]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8021
Unit selection: -
Expert list: 1
Factory setting
- [Arms]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [Vrms]
Access level: 2
Func. diagram: 8750, 8850,
8950
Unit selection: -
Expert list: 1
Factory setting
- [Arms]