2 Parameters
2.2 List of parameters
Bit 17 = 1 (enable signal missing), if:
- the commissioning mode is selected (p0009 > 0 or p0010 > 0) or there is an OFF2 fault response or the OFF1
signal source (p0840) is changed.
Bit 26 = 1 (enable signal missing), if:
- the infeed is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
Bit 29 = 1 (enable signal missing), if:
- the cooling unit ready signal via binector input p0266[1] missing.
r0047
Motor data identification and speed controller optimization / MotID and n_opt
VECTOR_G
Can be changed: -
Data type: Integer16
P-Group: Displays, signals
Not for motor type: -
Min
0
Description:
Displays the actual status for the motor data identification (stationary measurement) and the speed/velocity controller
optimization (rotating measurement).
Value:
0:
115:
120:
140:
150:
170:
190:
195:
200:
210:
220:
230:
240:
250:
260:
270:
290:
300:
Note:
For r0047 = 300:
This value is also displayed if encoder calibration p1990 is selected.
r0049[0...3]
Motor data set/encoder data set effective / MDS/EDS effective
VECTOR_G
Can be changed: -
Data type: Unsigned8
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays the effective Motor Data Set (MDS) and the effective Encoder Data Sets (EDS).
Index:
[0] = Motor Data Set MDS effective
[1] = Encoder 1 Encoder Data Set EDS effective
[2] = Encoder 2 Encoder Data Set EDS effective
[3] = Encoder 3 Encoder Data Set EDS effective
Dependency:
Refer to: p0186, p0187, p0188, p0189, r0838
Note:
Value 99 means the following: No encoder assigned (not configured).
60
No measurement
Measurement q leakage inductance (part 2)
Speed controller optimization (vibration test)
Calculate speed controller setting
Measurement moment of inertia
Measurement magnetizing current and saturation characteristic
Speed encoder test
Measurement q leakage inductance (part 1)
Rotating measurement selected
Pole position identification selected
identification leakage inductance
Identification rotor time constant
Identification stator inductance
Identification stator inductance LQLD
Identification circuit
Identification stator resistance
Identification valve lockout time
Stationary measurement selected
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
300
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 8565
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150