p1236[0...n]
Ext. armature short-cct. contactor feedback signal monit. time / ASC ext t_monit
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0 [ms]
Description:
Sets the monitoring time of the contactor feedback signal for the external armature short-circuit configuration.
If the contactor feedback signal (p1235) is parameterized, then the appropriate feedback signal (r1239.1) is expected
within this monitoring time after either opening or closing the contactor.
Dependency:
Refer to: p1230, p1231, p1235, p1237, r1239
Refer to: F07904, F07905
p1237[0...n]
External armature short-circuit delay time when opening / ASC ext t_wait
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0 [ms]
Description:
Sets the delay time when opening the contactor of the external armature short-circuit.
If no contactor feedback signal has been selected (p1235), then the system waits for this time before the pulses are
switched in.
Dependency:
Refer to: p1230, p1231, p1235, p1236, r1239
Notice:
This delay time must be at least long enough so that the contactor contacts reliably open before the pulses are
switched in. The delay time must be greater than the contactor response time. The Motor Module can be damaged if
the delay time is too short.
r1238
CO: Armature short-circuit external state / EASC state
VECTOR_G
Can be changed: -
Data type: Integer16
P-Group: Functions
Not for motor type: ASM
Min
0
Description:
Displays the state for the external armature short-circuit.
Value:
0:
1:
2:
3:
4:
5:
6:
Dependency:
Refer to: p1230, p1231, p1235, p1236, p1237, r1239
Refer to: F07904, F07905
Note:
Activation criterion (one of the following criteria is fulfilled):
- the signal at BI: p1230 (armature short-circuit activation) is 0.
- the drive is not in the state "S4: Operation" or in S5x (refer to function diagram 2610).
- the internal pulse enable is missing (r0046.19 = 0).
For state "switched out" (r1238 = 0):
- the external armature short-circuit can be selected with p1231 = 1.
For state "ready" (r1238 = 1):
- as soon as the activation criterion is fulfilled, then a transition is made into the state "active" (r1238 = 2).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Switched off
Ready
Active
Active - feedback signal "Closed" OK
Active - feedback signal "Closed" missing
Prompt to remove the armature short-circuit
Active - feedback signal "Open" missing
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
1000 [ms]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
1000 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
6
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
200 [ms]
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
200 [ms]
Access level: 1
Func. diagram: 2610
Unit selection: -
Expert list: 1
Factory setting
-
353