p9211
Flash function / Flash fct.
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: Topology
CU_G150_DP
Not for motor type: -
Min
-1
Description:
Sets the function for the component selected in p9210.
After initiating a function, the parameter is automatically reset again.
Example:
- set the component number (p9210).
- select the "flashing on" function (set p9211 = 1).
Value:
-1:
0:
1:
Dependency:
Refer to: p9210
Notice:
If a task cannot be executed (e.g. the component number in p9210 does not exist), the following applies:
- there is no negative feedback signal.
- the value is reset anyway.
r9220
Statistics number of entries / Stat entries qty
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
-
Description:
Displays the number of statistic entries in r9222.
Dependency:
In p9221, the component Id is set whose statistical entries are to be displayed.
Refer to: p9221
p9221
Statistic components Id / Statistic comp Id
CU_G130_PN,
Can be changed: T
CU_G150_PN,
Data type: Unsigned8
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
0000 hex
Description:
Selects the component Id whose statistics are to be displayed in r9222.
r9222[0...n]
Statistic DRIVE-CLiQ acyclic communication / Statistic
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned32
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
-
Description:
Displays the statistics for the acyclic DRIVE-CLiQ communication of a component.
The component is preset in p9221.
The entry comprises the following elements:
Index 0: Parameter Id.
Index 1: Number of messages sent.
892
Select function
Flashing off
Flashing on
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
00FF hex
Calculated: -
Dyn. index: r9220
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-1
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0002 hex
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents