Siemens G130 List Manual page 219

Hide thumbs Also See for G130:
Table of Contents

Advertisement

r0499[0...2]
CO: Encoder diagnostic signal high word / Enc diag high word
VECTOR_G
Can be changed: -
Data type: Integer16
P-Group: Encoder
Not for motor type: -
Min
-
Description:
Displays the trace signal for encoder diagnostics (high component).
The signal to be output is selected in p0496.
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency:
Refer to: p0496, r0497, r0498
r0499
Encoder diagnostic signal high word / Enc diag high word
ENC
Can be changed: -
Data type: Integer16
P-Group: Encoder
Not for motor type: -
Min
-
Description:
Displays the trace signal for encoder diagnostics (high component).
The signal to be output is selected in p0496.
Dependency:
Refer to: p0496, r0497, r0498
p0500
Technology application / Tec application
VECTOR_G
Can be changed: C2(1, 5), T
Data type: Integer16
P-Group: Applications
Not for motor type: -
Min
0
Description:
Sets the technology application.
The parameter influences the calculation of open-loop and closed-loop control parameters that is e.g. initiated using
p0578.
Value:
0:
1:
2:
4:
5:
6:
Dependency:
Refer to: p2175, p2177
Note:
The calculation of parameters dependent on the technology application can be called up as follows:
- when exiting quick commissioning using p3900 > 0
- when writing p0340 = 1, 3, 5 (for p0500 = 6: p0340 = 1, 3, 4)
- when writing p0578 = 1
For p0500 = 0 and when the calculation is initiated, the following parameters are set:
- p1574 = 10 V (separately excited synchronous motor: 20 V)
- p1750.2 = 0
- p1802 = 4 (SVM/FLB without overcontrol)
- p1803 = 106 %
- p1610 = 50 %
- p1611 = 30 %
- p1310 = 50 %
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Standard drive (VECTOR)
Pumps and fans
Sensorless closed-loop control down to f = 0 (passive loads)
Dynamic in the field weakening range
Starting with a high break loose torque
High LoadMomInert
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
6
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
219

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents