2 Parameters
2.2 List of parameters
p9334[0...1]
SI Motion SLP upper limit values (Motor Module) / SI Mtn SLP uplimMM
VECTOR_G (Safety
Can be changed: C2(95)
rot)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
-2147000.000 [°]
Description:
Sets the upper limit for the function "Safely Limited Position" (SLP).
Index:
[0] = Limit value SLP1 (SE1)
[1] = Limit value SLP2 (SE2)
Dependency:
Refer to: p9501, p9535, p9562
Refer to: C01715
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The following applies to the setting of these limits:
- p9334[x] > p9335[x]
- p9334[x] must lie in the valid traversing range (-737280 ... 737280).
SLP: Safely Limited Position / SE: Safe software limit switches
p9335[0...1]
SI Motion SLP lower limit values (Motor Module) / SI Mtn SLPlowLimMM
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
-2147000.000 [mm]
Description:
Sets the lower limit for the function "Safely Limited Position" (SLP).
Index:
[0] = Limit value SLP1 (SE1)
[1] = Limit value SLP2 (SE2)
Dependency:
Refer to: p9501, p9534, p9562
Refer to: C01715
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The following applies to the setting of these limits:
- p9334[x] > p9335[x]
- p9335[x] must lie in the valid traversing range (-737280 ... 737280).
SLP: Safely Limited Position / SE: Safe software limit switches
p9335[0...1]
SI Motion SLP lower limit values (Motor Module) / SI Mtn SLPlowLimMM
VECTOR_G (Safety
Can be changed: C2(95)
rot)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
-2147000.000 [°]
Description:
Sets the lower limit for the function "Safely Limited Position" (SLP).
Index:
[0] = Limit value SLP1 (SE1)
[1] = Limit value SLP2 (SE2)
Dependency:
Refer to: p9501, p9534, p9562
Refer to: C01715
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The following applies to the setting of these limits:
- p9334[x] > p9335[x]
- p9335[x] must lie in the valid traversing range (-737280 ... 737280).
SLP: Safely Limited Position / SE: Safe software limit switches
904
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2147000.000 [°]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2147000.000 [mm]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2147000.000 [°]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2822
Unit selection: -
Expert list: 1
Factory setting
100000.000 [°]
Access level: 3
Func. diagram: 2822
Unit selection: -
Expert list: 1
Factory setting
-100000.000 [mm]
Access level: 3
Func. diagram: 2822
Unit selection: -
Expert list: 1
Factory setting
-100000.000 [°]