2 Parameters
2.2 List of parameters
For p8809[8...53]:
Reserved.
p8811
SINAMICS Link project selection / Project sel
CU_G130_PN (PN
Can be changed: C1(1)
CBE20),
Data type: Integer16
CU_G150_PN (PN
P-Group: Communications
CBE20),
Not for motor type: -
CU_G130_DP (PN
CBE20),
Min
CU_G150_DP (PN
8
CBE20)
Description:
Project selection for SINAMICS Link.
Value:
8:
12:
16:
64:
Note:
SINAMICS Link requires that the appropriate CBE20 firmware version is selected (p8835 = 3).
The parameter must be set the same for all participants.
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
p8812[0...1]
SINAMICS Link clock cycle settings / Clock cyc set
CU_G130_PN (PN
Can be changed: C1(1)
CBE20),
Data type: Unsigned16
CU_G150_PN (PN
P-Group: Communications
CBE20),
Not for motor type: -
CU_G130_DP (PN
CBE20),
Min
CU_G150_DP (PN
0
CBE20)
Description:
Sets the clock cycle for SINAMICS Link.
For index 0:
0 = clock synchronous mode not activated, 1 = clock synchronous mode activated
For index 1:
Possible values: 500, 1000, 2000 µs
Index:
[0] = Activate isochronous mode
[1] = Bus CC [µs]
Dependency:
Refer to: p8811
Note:
SINAMICS Link requires that the appropriate CBE20 firmware version is selected (p8835 = 3).
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
For index 0:
Is applicable for the synchronization of the application. The SINAMICS Link itself is always synchronous.
For index 1:
The value must be set the same for all participants.
When newly selecting the project p8811, p8812[1] is set to the factory setting.
For p8811 = 8, 12, 16 the following applies:
Min/max/factory setting: 500/500/500 µs
For p8811 = 64, the following applies:
Min/max/factory setting: 1000/2000/2000 µs
838
Project 8 participants, 32 words
Project 12 participants, 24 words
Project 16 participants, 16 words
Project 64 participants, 16 words
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
64
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2000
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2197, 2198
Unit selection: -
Expert list: 1
Factory setting
64
Access level: 3
Func. diagram: 2197, 2198
Unit selection: -
Expert list: 1
Factory setting
[0] 1
[1] 2000