2 Parameters
2.2 List of parameters
It is calculated as follows:
r = 0.0001 x max(p2237, |p2238|) [%] / 0.13^2 [s^2]
The jerk is effective until the maximum acceleration is reached (a_max = p2237 [%] / p2247 [s] or a_max = p2238 [%]
/ p2248 [s]), after which the drive continues to run linearly with constant acceleration.
The higher the maximum acceleration (the lower that p2247 is), the longer the ramp-up time increases with respect to
the set ramp-up time.
For bit 03:
0: Non-volatile data save deactivated.
1. The setpoint for the motorized potentiometer is saved in a non-volatile fashion (for p2230.0 = 1).
For bit 04:
When the bit is set, the ramp-function generator is computed independent of the pulse enable. The actual output
value of the motorized potentiometer is always in r2250.
r2231
Technology controller motorized potentiometer setpoint memory / Tec_ctrl mop mem
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
- [%]
Description:
Displays the setpoint memory for the motorized potentiometer of the technology controller.
For p2230.0 = 1, the last setpoint that was saved is entered after ON.
Dependency:
Refer to: p2230
p2235[0...n]
BI: Technology controller motorized potentiometer raise setpoint / Tec_ctrl mop raise
VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source to continually increase the setpoint for the motorized potentiometer of the technology
controller.
The setpoint change (CO: r2250) depends on the set ramp-up time (p2247) and the duration of the signal that is
present (BI: p2235).
Dependency:
Refer to: p2236
p2236[0...n]
BI: Technology controller motorized potentiometer lower setpoint /
Tec_ctrl mop lower
VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source to continually reduce the setpoint for the motorized potentiometer of the technology controller.
The setpoint change (CO: r2250) depends on the set ramp-down time (p2248) and the duration of the signal that is
present (BI: p2236).
Dependency:
Refer to: p2235
568
Calculated: -
Dyn. index: -
Unit group: 9_1
Scaling: -
Max
- [%]
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: 7954
Unit selection: p0595
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 7954
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 7954
Unit selection: -
Expert list: 1
Factory setting
0