2 Parameters
2.2 List of parameters
Notice:
After fault F07320 occurs, the switch-on command must be withdrawn and all of the faults acknowledged so that the
automatic restart function is re-activated.
After a complete power failure (blackout) the start counter always starts with the counter value that applied before the
power failure, and decrements this start attempt by 1. If a further attempt to acknowledge is started by the automatic
restart function prior to power failure, e.g. when the CU remains active on power failure longer than the time p1212 /
2, the fault counter will already have been decremented once. In this case, the start counter is thus decreased by the
value 2.
Note:
A start attempt starts immediately when a fault occurs. The start attempt is considered to been completed if the motor
was magnetized (r0056.4 = 1) and an additional delay time of 1 s has expired.
As long as a fault is present, an acknowledge command is generated in the time intervals of p1212 / 2. When
successfully acknowledged, the start counter is decremented. If, after this, a fault re-occurs before a restart has been
completed, then acknowledgment starts again from the beginning.
Fault F07320 is output if, after several faults occur, the number of parameterized start attempts has been reached.
After a successful start attempt, i.e. a fault/error has no longer occurred up to the end of the magnetizing phase, the
start counter is again reset to the parameter value after 1 s. If a fault re-occurs - the parameterized number of start
attempts is again available.
At least one start attempt is always carried out.
After a line supply failure, acknowledgment is immediate and when the line supply returns, the system is switched on.
If, between successfully acknowledging the line fault and the line supply returning, another fault occurs, then its
acknowledgment also causes the start counter to be decremented.
p1211
Automatic restart start attempts / AR start attempts
B_INF
Can be changed: U, T
Data type: Unsigned16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the start attempts of the automatic restart function for p1210 = 4, 6.
Dependency:
This parameter setting is active for p1210 = 6.
For p1210 = 4, the parameter only has an influence if, when attempting to start, an additional line phase failure
(F06200) occurs.
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Refer to: p1210, r1214
Refer to: F07320
Notice:
After fault F07320 occurs, the switch-on command must be withdrawn and all of the faults acknowledged so that the
automatic restart function is re-activated.
After a complete power failure (blackout) the start counter always starts with the counter value that applied before the
power failure, and decrements this start attempt by 1. If a further attempt to acknowledge is started by the automatic
restart function prior to power failure, e.g. when the CU remains active on power failure longer than the time p1212 /
2, the fault counter will already have been decremented once. In this case, the start counter is thus decreased by the
value 2.
Note:
A start attempt starts immediately when a fault occurs. The restart attempt is considered to have been completed if
the infeed is switched on and an additional delay time of 1 s has expired.
As long as a fault is present, an acknowledge command is generated in the time intervals of p1212 / 2. When
successfully acknowledged, the start counter is decremented. If, after this, a fault re-occurs before a restart has been
completed, then acknowledgment starts again from the beginning.
Fault F07320 is output if, after several faults occur, the number of parameterized start attempts has been reached.
After a successful start attempt (i.e. a fault/error has no longer occurred up to the end of the switching-on operation)
the start counter is again reset to the parameter value after 1 s. If faults re-occur, the parameterized number of start
attempts is again available.
At least one start attempt is always carried out.
After a line supply failure, acknowledgment is immediate and when the line supply returns, the system is switched on.
If, between successfully acknowledging the line fault and the line supply returning, another fault occurs, then its
acknowledgment also causes the start counter to be decremented.
340
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
3
SINAMICS G130/G150