2 Parameters
2.2 List of parameters
r3687
BO: Digital Braking Module pre-alarm overtemperature / Dig BM A overtemp
B_INF
Can be changed: -
Data type: Unsigned32
P-Group: -
Not for motor type: -
Min
-
Description:
Displays a fault due to the excessively high temperature.
1 signal:
The connected temperature sensor (X21.1, X21.2) signals an overtemperature.
Recommendation:
Measure the braking resistor temperature using the temperature sensor.
r3688
BO: Braking Module internal overtemperature shutdown / BM int temp shutd
B_INF
Can be changed: -
Data type: Unsigned32
P-Group: -
Not for motor type: -
Min
-
Description:
Displays the shutdown due to the excessively high temperature.
1 signal:
The connected temperature sensor (X21.1, X21.2) signals an overtemperature. The highest permissible temperature
at the connected temperature sensor has been exceeded and results in a shutdown.
Dependency:
Refer to: F06908
r3689
BO: Digital Braking Module Uce fault / Dig BM Uce fault
B_INF
Can be changed: -
Data type: Unsigned32
P-Group: -
Not for motor type: -
Min
-
Description:
Displays an Uce fault in the internal Braking Module.
1 signal:
An Uce fault is present in the internal Braking Module.
Dependency:
Refer to: F06909
p3800[0...n]
Sync-line-drive activation / Sync act
VECTOR_G
Can be changed: T
Data type: Integer16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the activation for the line-drive synchronization.
Value:
0:
1:
Dependency:
Refer to: p3801, p3802
Caution:
If there is only one VSM being used, this can either be used for line synchronization or for a flying restart. If the VSM
was connected to the line supply, then flying restart should be deselected in p1200. If the VSM was connected at the
output (motor side), then line synchronization should be deactivated using p3800.
Line synchronization (first VSM connected with the line supply) and also flying restart (second VSM connected to the
motor terminals) can only be used if two VSMs are assigned to the Motor Module.
616
Sync-line-drive deactivated
Sync-line-drive activated VSM-INT
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150