p0092
Clock synchronous operation pre-assignment/check / Cl sync op pre-as
CU_G130_PN,
Can be changed: C1(1)
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
0
Description:
Setting to pre-assign/check the sampling times for the internal controller clock cycles for clock-synchronous
PROFIdrive operation.
For p0092 = 1:
The controller clock cycles are set so that clock synchronous PROFIdrive operation is possible. If it is not possible to
change the controller clock cycles of the clock-cycle synchronous PROFIdrive operation, then an appropriate
message is output.
The pre-setting of the controller clock cycles can result in a derating of the Motor Module (e.g. p0115[0] = 400 µs -->
375 µs).
When calculating the drive unit utilization (r9976), when using the fixed DCC runtime groups "Receive AFTER IF1
PROFIdrive PZD", "Send BEFORE IF1 PROFIdrive PZD", "Receive AFTER IF2 PZD" (from V4.4) and "Send
BEFORE IF2 PZD" (from V4.4), then its maximum computing time load has already been calculated during ramp-up
for isochronous operation and taken into account in r9976 (from V4.3).
For p0092 = 0:
The controller clock cycles are set without any restrictions by the clock-cycle PROFIdrive operation (same as for up
to V2.3).
When calculating the drive unit utilization (r9976), when using the fixed DCC runtime groups "Receive AFTER IF1
PROFIdrive PZD", "Send BEFORE IF1 PROFIdrive PZD", "Receive AFTER IF2 PZD" (from V4.4) and "Send
BEFORE IF2 PZD" (from V4.4), then its maximum computing time load has already been calculated during ramp-up
for isochronous operation and taken into account in r9976 (from V4.3).
Value:
0:
1:
Dependency:
Refer to: r0110, p0115
Refer to: A01223, A01224
Caution:
Only current controller sampling times (p0115[0]) which are integers of 125 µs are permitted for isochronous mode.
For SERVO the following current controller sampling times are also possible:
187.5, 150, 100, 93.75, 75, 62.5, 50, 37.5, 31.25 µs
For VECTOR the following current controller sampling times are also possible:
312.5, 218.75, 200, 187.5, 175, 156.25, 150, 137.5 µs
The additional current controller sampling times must be taken into account when parameterizing the bus for Ti, To
and Tdp.
Notice:
p0092 only affects the automatic default for the sampling times (p0115) in the drive.
If the sampling times are modified subsequently in expert mode (p0112 = 0), p0092 = 0 should be set so that the new
values are not overwritten again by the automatic default when the parameters are downloaded.
The conditions for current controller sampling time for isosynchronous operation must still be carefully ensured (refer
under Caution!).
r0094
CO: Transformation angle / Transformat_angle
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [°]
Description:
Displays the transformation angle.
Dependency:
Refer to: p0431, r1778
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
No isochronous PROFIBUS
Isochronous PROFIBUS
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2005
Max
- [°]
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 4700, 4702,
4710, 6300, 6714, 6730, 6731,
6732
Unit selection: -
Expert list: 1
Factory setting
- [°]
71