2 Parameters
2.2 List of parameters
p1000[0...n]
Macro Connector Inputs (CI) for speed setpoints / Macro CI n_set
VECTOR_G
Can be changed: C2(1), T
Data type: Unsigned32
P-Group: Commands
Not for motor type: -
Min
0
Description:
Runs the corresponding macro files.
The Connector Inputs (CI) for the speed setpoints of the appropriate Command Data Set (CDS) are appropriately
interconnected.
The selected macro file must be available on the memory card/device memory.
Example:
p1000 = 6 --> the macro file PM000006.ACX is run.
Dependency:
Refer to: p0015, p0700, p1500, r8572
Notice:
No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
The macros in the specified directory are displayed in r8572. r8572 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
CI: Connector Input
p1001[0...n]
CO: Fixed speed setpoint 1 / n_set_fixed 1
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-210000.000 [rpm]
Description:
Setting and connector output for fixed speed setpoint 1.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1002[0...n]
CO: Fixed speed setpoint 2 / n_set_fixed 2
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-210000.000 [rpm]
Description:
Setting and connector output for fixed speed setpoint 2.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1003[0...n]
CO: Fixed speed setpoint 3 / n_set_fixed 3
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-210000.000 [rpm]
Description:
Setting and connector output for fixed speed setpoint 3.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
306
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
999999
Calculated: -
Dyn. index: DDS, p0180
Unit group: 3_1
Scaling: p2000
Max
210000.000 [rpm]
Calculated: -
Dyn. index: DDS, p0180
Unit group: 3_1
Scaling: p2000
Max
210000.000 [rpm]
Calculated: -
Dyn. index: DDS, p0180
Unit group: 3_1
Scaling: p2000
Max
210000.000 [rpm]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 3010
Unit selection: p0505
Expert list: 1
Factory setting
0.000 [rpm]
Access level: 2
Func. diagram: 3010
Unit selection: p0505
Expert list: 1
Factory setting
0.000 [rpm]
Access level: 2
Func. diagram: 3010
Unit selection: p0505
Expert list: 1
Factory setting
0.000 [rpm]
SINAMICS G130/G150