Siemens G130 List Manual page 440

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p1699 = 1:
The new filter data are only accepted when this parameter is reset.
Dependency:
Speed setpoint filter 1, 2 (p1414 and following)
Current setpoint filter 1 ... 4 (p1656 and following)
Current setpoint filter 5 ... 10 (function module, p5200 and following)
Refer to: p1656
p1702[0...n]
Isd current controller pre-control scaling / Isd_ctr_prectrScal
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: ASM, REL
Min
0.0 [%]
Description:
Sets the scaling of the dynamic current controller pre-control for the flux-generating current component Isd.
Note:
The parameter is effective for permanent and separately excited synchronous motors.
p1703[0...n]
Isq current controller pre-control scaling / Isq_ctr_prectrScal
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.0 [%]
Description:
Sets the scaling of the dynamic current controller pre-control for the torque/force-generating current component Isq.
p1704[0...n]
Isq current controller pre-control EMF scaling / Isq_ctrl EMF scal
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: ASM, PMSM, REL
Min
0.0 [%]
Description:
Sets the scaling of the EMF pre-control for the Isq current controller.
p1705[0...n]
Flux setpoint/actual value tracking threshold / Flux track thresh
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: ASM, PMSM, REL
Min
0.0 [%]
Description:
Threshold for the setpoint - actual value tracking of the EMF pre-control of the Isq current controller.
440
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
200.0 [%]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
200.0 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
200.0 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
100.0 [%]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 4
Func. diagram: 6714
Unit selection: -
Expert list: 1
Factory setting
70.0 [%]
Access level: 4
Func. diagram: 6714
Unit selection: -
Expert list: 1
Factory setting
70.0 [%]
Access level: 4
Func. diagram: 6714, 6726
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]
Access level: 4
Func. diagram: 6714, 6726
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150