p3135
Suppress active fault / Supp act flt
VECTOR_G, B_INF
Can be changed: U, T
Data type: Unsigned32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Sets the suppression of r2139.3 "Fault present" for certain fault responses.
Bit field:
Bit
08
10
Dependency:
Refer to: p0491, r2139
Note:
Depending on the suppression of a fault reaction in this parameter, r2139.1 "Acknowledgment required" is set when
at least one fault occurs.
For bit 08:
The suppression is only effective if p0491 = 1.
p3201[0...n]
Excitation current outside the tolerance threshold value / I_exc n Tol thresh
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: ASM, PMSM, REL,
RESM
Min
0.1 [%]
Description:
Sets the threshold value for the "excitation current outside tolerance" message for the excitation current monitoring.
If the absolute value of the difference between the excitation current setpoint and actual value (r1641 - r1626)
exceeds the threshold value and the hysteresis is longer than the selected delay time, then fault F07913 is output.
This fault is withdrawn when the threshold voltage is undershot.
Dependency:
Refer to: r1626, r1641, p3202, p3203
Refer to: F07913
Note:
The monitoring function is only carried out for separately excited synchronized motors (p0300 = 5).
p3202[0...n]
Excitation current outside the tolerance hysteresis / I_exc n Tol hyst
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: ASM, PMSM, REL,
RESM
Min
0.1 [%]
Description:
Sets the hysteresis for the "excitation current outside tolerance" message for the excitation current monitoring.
Dependency:
Refer to: p3201, p3203
Refer to: F07913
Note:
The monitoring function is only carried out for separately excited synchronized motors (p0300 = 5).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Suppression of fault response ENCODER
Suppression of fault response NONE
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
ON
ON
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.0 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.0 [%]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: 8060
Unit selection: -
Expert list: 1
Factory setting
0000 0000 0000 0000 bin
0 signal
OFF
OFF
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
10.0 [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
10.0 [%]
FP
-
-
597