Page 3
___________________ Sinusoidal filter Safety information ___________________ General ___________________ Mechanical installation SINAMICS ___________________ Electrical installation SINAMICS G130 ___________________ Sine-wave filter Technical specifications Operating Instructions Control version V4.3 SP2 Siemens Industrial 05/2010 A5E00992420A...
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
3. Make sure that the equipment is de-energized. 4. Ground and short-circuit. 5. Cover or enclose adjacent components that are still live. NOTICE For a UL-approved system use 60/75°C copper conductors only. Sine-wave filter Siemens Industrial Operating Instructions, 05/2010, A5E00992420A...
The operating manual and machine documentation are written in different languages as specified in the delivery contracts. Note We recommend engaging the support and services of your local Siemens service center for all planning, installation, commissioning and maintenance work. Sine-wave filter...
● c = ESD shoes ● d = ESD overall ● e = ESD wristband ● f = cabinet ground connection ● g = contact with conductive flooring Figure 1-1 ESD protective measures Sine-wave filter Siemens Industrial Operating Instructions, 05/2010, A5E00992420A...
Page 10
Safety information 1.3 Components that can be destroyed by electrostatic discharge (ESD) Sine-wave filter Operating Instructions, 05/2010, A5E00992420A...
1U2, 1V2, 1W2. If this is not observed, the sine-wave filter may be damaged. CAUTION If sine-wave filters that have not been approved for SINAMICS by SIEMENS are used, the Power Modules may be damaged or may malfunction. CAUTION The surface temperature of the sine-wave filters can exceed 80°C.
Page 12
Note If a filter cannot be parameterized (p0230 ≠ 3) during commissioning, then no provision is made for this SIEMENS sine-wave filter for the SINAMICS G130. Sine-wave filter Operating Instructions, 05/2010, A5E00992420A...
Page 13
General Table 2- 2 Technical specifications for sine-wave filters with SINAMICS G130 Order number Voltage Pulse frequency Output current SINAMICS G130 [kHz] 6SL3310-1GE32-1AAx 3 AC 380 – 480 172 A 6SL3310-1GE32-6AAx 3 AC 380 – 480 216 A 6SL3310-1GE33-1AAx 3 AC 380 – 480...
Page 14
General Sine-wave filter Operating Instructions, 05/2010, A5E00992420A...
To reduce the risk of fire or an electric shock, the current-conducting parts and other components in the built-in unit should be inspected and damaged parts replaced. When an item of protective gear trips, the cause of the trip must be identified and rectified. Sine-wave filter Siemens Industrial Operating Instructions, 05/2010, A5E00992420A...
Page 18
Electrical installation Connection When connecting the sine-wave filter, you must take into account the following conditions to ensure that the filter functions correctly: ● With analog control cables, connecting the shield at both ends can result in coupled-in noise. To prevent this, the shield must only be connected at one end on the Power Module.
10 m/s² at >9 ... 200 Hz 10 m/s² at >58 ... 200 Hz Shock load: - Acceleration 40 m/s² at 22 ms 100 m/s² at 11 ms 100 m/s² at 11 ms In transport packaging Sine-wave filter Siemens Industrial Operating Instructions, 05/2010, A5E00992420A...
Page 20
Technical specifications Detailed technical specifications Table 5- 2 Technical specifications of sine-wave filter 380 V – 480 V 3 AC Order number 6SL3000- 2CE32-3AA0 2CE32-3AA0 2CE32-8AA0 2CE33-3AA0 2CE34-1AA0 Suitable for Power 6SL3310- 1GE32-1AAx 1GE32-6AAx 1GE33-1AAx 1GE33-8AAx 1GE35-0AAx Module Rated current (unit 170 A 215 A 270 A...
Page 21
- to the Power Module - load - PE Max. permissible cable 300 (shielded) length between sine- 450 (unshielded) wave filter and motor Degree of protection IP00 IP00 Dimensions Width Height Depth Weight Sine-wave filter Siemens Industrial Operating Instructions, 05/2010, A5E00992420A...