2 Parameters
2.2 List of parameters
For bit 03 = 1:
The DC link voltage limit is set to the maximum value of the power unit.
For bit 05 = 1:
The status of the inputs/outputs for the power unit contactors is displayed in r0256.
This only applies to chassis power units with 3 AC line connection and line contactors.
The status display is only effective after parameter save and POWER ON.
p0212
Power unit configuration / PU config
VECTOR_G (n/M)
Can be changed: C2(2)
Data type: Unsigned16
P-Group: Converter
Not for motor type: -
Min
-
Description:
Sets the power unit configuration.
Bit field:
Bit
00
01
03
05
06
Dependency:
For bit 00:
Reduced supply voltages are only possible for booksize and chassis power units (DC/AC).
Bit 0 = 1 can only be set if r0192.22 = 1.
For bit 01 = 1:
The external precharging setting only affects the DC/AC power units.
For bit 03 = 1:
The automatic adaptation (reduction) of the Vdc max limit is deactivated (only for chassis power units). Bit 3 only has
an effect, if bit 0 is simultaneously set.
Refer to: r0192, p0210
Caution:
For bit 00:
Working with reduced input voltages deactivates undervoltage detection.
For bit 03:
If the automatic setting of the Vdc max limit is deactivated, then all of the components connected to the DC link must
be suitable for the maximum DC link voltage of the power unit (e.g. 820 V for 400 V units).
Note:
For bit 00 = 0:
It is not possible to reduce the supply voltage in p0210.
For bit 00 = 1:
With this setting the supply voltage in p0210 can be reduced to 100 V.
Booksize PU: only for operating mode p1300 = 19
Chassis PU: only for operating mode p1300 > 19 and closed-loop DC voltage control
For bit 01 = 0:
There is no external precharging of the DC/AC Motor Modules. The precharging monitoring is bypassed.
For bit 01 = 1:
There is external precharging of the DC/AC Motor Modules. The precharging monitoring is calculated.
For bit 03 = 0:
The DC link voltage limit is calculated from p0210.
For bit 03 = 1:
The DC link voltage limit is set to the maximum value of the power unit.
For bit 05 = 1:
The status of the inputs/outputs for the power unit contactors is displayed in r0256.
This only applies to chassis power units with 3 AC line connection and line contactors.
The status display is only effective after parameter save and POWER ON.
116
Signal name
Drive unit line supply voltage reduced
External precharging present
Automatically adapt Vdc_max limit
Contactor display inputs/outputs status
Reduction of the permissible minimum
voltage during precharging
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
No
Yes
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 0000 bin
0 signal
No
No
Yes
No
No
SINAMICS G130/G150
FP
-
-
-
9814
-