r0313[0...n]
Motor pole pair number, actual (or calculated) / Mot PolePairNo act
VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Motor
Not for motor type: -
Min
-
Description:
Displays the number of motor pole pairs. The value is used for internal calculations.
r0313 = 1: 2-pole motor
r0313 = 2: 4-pole motor, etc.
Dependency:
For p0314 > 0, the entered value is displayed in r0313.
For p0314 = 0, the pole pair number (r0313) is automatically calculated from the rated power (p0307), rated
frequency (p0310) and rated speed (p0311).
Refer to: p0307, p0310, p0311, p0314
Note:
For the automatic calculation, the pole pair number is set to the value of 2 if the rated speed or the rated frequency is
zero.
p0314[0...n]
Motor pole pair number / Mot pole pair No.
VECTOR_G
Can be changed: C2(1, 3)
Data type: Unsigned16
P-Group: Motor
Not for motor type: -
Min
0
Description:
Sets the motor pole pair number.
p0314 = 1: 2-pole motor
p0314 = 2: 4-pole motor, etc.
Dependency:
For p0314 = 0, the pole pair number is automatically calculated from the rated frequency (p0310) and the rated
speed (p0311) and displayed in r0313.
Notice:
If p0314 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly. This is not the case when commissioning the motor (p0010 =
3).
For induction motors, the value need only be input if the rated data of a generator is entered therefore resulting in a
negative rated slip. In this case, the number of pole pairs in r0313 is too low by 1 and must be manually corrected.
p0316[0...n]
Motor torque constant / Mot kT
VECTOR_G
Can be changed: C2(1, 3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, SESM, REL,
RESM
Min
0.000 [Nm/A]
Description:
Sets the torque constant of the synchronous motor.
p0316 = 0:
The torque constant is calculated from the motor data.
p0316 > 0:
The selected value is used as torque constant.
Dependency:
Refer to: r0334
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
This parameter is not used for induction motors (p0300 = 1xx).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: MDS, p0130
Unit group: 28_1
Scaling: -
Max
400.000 [Nm/A]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 5300
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: p0100
Expert list: 1
Factory setting
0.000 [Nm/A]
135