2 Parameters
2.2 List of parameters
Note:
KHP: Know-How Protection
p7759[0...19]
KHP Control Unit reference serial number / KHP CU ref ser_no
CU_G130_PN,
Can be changed: T
CU_G150_PN,
Data type: Unsigned8
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the reference serial number for the Control Unit.
Using this parameter, if a Control Unit and/or a memory card is replaced at the end customer, the OEM can again
adapt the project to the modified hardware.
Dependency:
Refer to: p7765, p7766, p7767, p7768
Note:
KHP: Know-How Protection
- the OEM may only change this parameter for the use case "Sending encrypted SINAMICS data".
- SINAMICS only evaluates this parameter when powering up from the encrypted "Load into file system..." output or
when powering up from the encrypted PS files. The evaluation is only made when know-how protection and memory
card copy protection have been activated.
r7760.0...12
CO/BO: Write protection/know-how protection status / Wr_prot/KHP stat
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
-
Description:
Displays the status for the write protection and know-how protection.
Bit field:
Bit
00
01
02
03
04
05
06
12
Dependency:
Refer to: p7761, p7765, p7766, p7767, p7768
Note:
KHP: Know-How Protection
For bit 00:
Write protection can be activated/deactivated via p7761 on the Control Unit.
For bit 01:
The know-how protection can be activated by entering a password (p7766 ... p7768).
For bit 02:
If it has already been activated, know-how protection can be temporarily deactivated by entering the valid password
in p7766. In this case, bit 1 = 0 and bit 2 = 1 offset.
For bit 03:
Know-how protection cannot be deactivated, as p7766 is not entered in the OEM exception list (only the factory
setting is possible). This bit is only set if know-how protection is active (bit 1 = 1) and p7766 has not been entered in
the OEM exception list.
For bit 04:
When know-how protection has been activated, the contents of the memory card (parameter and DCC data) can be
additionally protected against being used with other memory cards/Control Units. This bit is only set if know-how
protection is active and in p7765.0 is set = 1.
770
Signal name
Write protection active
Know-how protection active
Know-how protection temporarily withdrawn Yes
Know-how protection cannot be deactivated Yes
Extended copy protection is active
Basic copy protection is active
Trace and measuring functions for
diagnostic purposes active
Reserved Siemens
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
SINAMICS G130/G150
FP
-
-
-
-
-
-
-
-