p0234
Power unit sine-wave filter capacitance / PU sine filter C
VECTOR_G
Can be changed: C2(2), U, T
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
0.000 [µF]
Description:
Enters the capacitance of a sine-wave filter connected at the power unit output.
Dependency:
This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
Refer to: p0230
Note:
The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined
SIEMENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside
the commissioning phase (p0010 = 0).
p0235
Motor reactor in series number / L_mot in SeriesQty
VECTOR_G
Can be changed: C2(1, 2)
Data type: Unsigned8
P-Group: Converter
Not for motor type: -
Min
1
Description:
Sets the number of reactors connected in series at the power unit output.
Dependency:
Refer to: p0230
Notice:
If the number of motor reactors connected in series does not correspond to this parameter value, then this can result
in an unfavorable control behavior.
r0238
Internal power unit resistance / PU R internal
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [ohm]
Description:
Displays the internal resistance of the power unit (IGBT and line resistance).
Note:
For a parallel circuit, the value corresponds to the resistance of a power unit.
p0247
Voltage measurement configuration / U_mes config
VECTOR_G
Can be changed: C2(2), U, T
Data type: Unsigned32
P-Group: Converter
Not for motor type: -
Min
-
Description:
Sets the configuration for the voltage measurement.
Bit field:
Bit
05
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Use voltage measured values for flying
restart
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000.000 [µF]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [ohm]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.000 [µF]
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [ohm]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 0000 bin
0 signal
No
FP
-
119