r9708[0...5]
SI Motion diagnostics safe position / SI mtn safe pos
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
- [mm]
Description:
Displays the actual load-side actual values of both monitoring channels and their difference.
Index:
[0] = Load-side actual value on the CU
[1] = Load-side actual value on the second channel
[2] = Load-side actual value difference CU - second channel
[3] = Load-side max. actual value difference CU - second channel
[4] = Load-side actual value as safe position via PROFIsafe
[5] = Load-side additional actual value difference CU - second channel
Dependency:
Refer to: r9713
Note:
For index 0:
The display of the load-side position actual value on the Control Unit is updated in the monitoring clock cycle.
For index 1:
The display of the load-side position actual value on the second channel is updated in the CDC clock cycle (r9724)
and delayed by one CDC clock cycle.
For index 2:
The difference between the load-side position actual value on the Control Unit and load-side position actual value in
the second channel is updated in the CDC clock cycle (r9724) and delayed by one CDC clock cycle.
For index 3:
The maximum difference between the load-side position actual value on the Control Unit and the load-side position
actual value on the second channel.
For index 4:
Displays the load-side position actual value when enabling the function "Safe position via PROFIsafe".
The value is an average value from the values in index 0 and 1.
When the function is not enabled, the content corresponds to the value in index 0.
For index 5:
The display of the maximum additional difference between the load-side position actual value on the Control Unit,
and the load-side position actual value in the second channel, which can occur as a result of the actual value sensing
delay in the EnDat 2.2 converter.
Input in p9542: p9708[3] + p9708[5], after performing the measurement for the mechanical tolerance by performing a
test run, where, after completion, the maximum tolerance that has occurred is displayed in p9708[3].
CDC: Crosswise Data Comparison
r9708[0...5]
SI Motion diagnostics safe position / SI mtn safe pos
VECTOR_G (Safety
Can be changed: -
rot)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
- [°]
Description:
Displays the actual load-side actual values of both monitoring channels and their difference.
Index:
[0] = Load-side actual value on the CU
[1] = Load-side actual value on the second channel
[2] = Load-side actual value difference CU - second channel
[3] = Load-side max. actual value difference CU - second channel
[4] = Load-side actual value as safe position via PROFIsafe
[5] = Load-side additional actual value difference CU - second channel
Dependency:
Refer to: r9713
Note:
For index 0:
The display of the load-side position actual value on the Control Unit is updated in the monitoring clock cycle.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [mm]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [°]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2822, 2836
Unit selection: -
Expert list: 1
Factory setting
- [mm]
Access level: 3
Func. diagram: 2822, 2836
Unit selection: -
Expert list: 1
Factory setting
- [°]