Siemens G130 List Manual page 451

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p1756
Motor model changeover speed hysteresis encoderless operation /
MotMod n_chgov hys
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.0 [%]
Description:
Sets the hysteresis for the changeover speed of the motor model for encoderless operation.
In the case of separately excited synchronous motors, the lower hysteresis value is calculated with p1756 * p1755; in
the case of all other types of motor, p1755 * (1 - p1756) is used.
Dependency:
In U/f characteristic mode the parameter is of no significance.
Refer to: p1755
Note:
The parameter value refers to p1755.
In the case of separately excited synchronous motors, the lower hysteresis value is calculated with p1755 * p1756; in
the case of all other types of motor, p1755 * (1 - p1756) is used.
p1757[0...n]
Motor model w/o enc. op./cl.-loop controlled stab. controller Kp / MotMod w/o enc Kp
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: SESM, REL
Min
0.01
Description:
Sets the gain of the transient response controller when the motor model changes over from open-loop controlled
operation to closed-loop controlled operation.
Note:
Only for ASM and PSM in encoderless operation:
The settling range starts at 0.5 * p1755 * p1756.
For ASM it ends at p1755 * p1756 or at p1755, if p1759 is at the maximum value.
For PSM it always ends at p1755 * p1756.
p1758[0...n]
Motor model changeover delay time closed/open-loop control / MotMod t cl_op
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: PMSM, SESM, REL
Min
100 [ms]
Description:
Sets the minimum time for falling below the changeover speed when changing from closed-loop controlled operation
to open-loop controlled operation.
Dependency:
The wait time has no significance if the setpoint speed before the ramp-function generator lies in the open-loop
speed controlled operating range. In this case, the change is made without any delay.
Refer to: p1755, p1756
Note:
If p1758 is changed, commissioning must be selected in order to validate the value for the blocking monitoring.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: CALC_MOD_REG
Dyn. index: -
Unit group: -
Scaling: -
Max
95.0 [%]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10.00
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000 [ms]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6730, 6731,
6732, 6733
Unit selection: -
Expert list: 1
Factory setting
50.0 [%]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.70
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1000 [ms]
451