2 Parameters
2.2 List of parameters
p0418[0...n]
Fine resolution Gx_XIST1 (in bits) / Enc fine Gx_XIST1
VECTOR_G, ENC
Can be changed: C2(4)
Data type: Unsigned8
P-Group: Encoder
Not for motor type: -
Min
2
Description:
Sets the fine resolution in bits of the incremental position actual values.
Note:
The parameter applies for the following process data:
- Gx_XIST1
- Gx_XIST2 for reference mark or flying measurement
The fine resolution specifies the fraction between encoder pulses. Depending on the physical measurement principle,
an encoder pulse can be broken down into a different number of fractions (e.g. squarewave encoder: 2 bit =
resolution 4, sin/cos encoder: Typical 11 bit = resolution 2048).
For a squarewave encoder, with the factory setting, the least significant bits have the value zero, i.e. they do not
supply any useful information.
For especially high quality measuring systems, the fine resolution must be increased corresponding to the available
accuracy.
p0419[0...n]
Fine resolution absolute value Gx_XIST2 (in bits) / Enc fine Gx_XIST2
VECTOR_G, ENC
Can be changed: C2(4)
Data type: Unsigned8
P-Group: Encoder
Not for motor type: -
Min
2
Description:
Sets the fine resolution in bits of the absolute position actual values.
Dependency:
Refer to: p0418
Note:
This parameter applies to process data Gx_XIST2 when reading the absolute value.
p0420[0...n]
Encoder connection / Enc_connection
VECTOR_G, ENC
Can be changed: C2(4)
Data type: Unsigned16
P-Group: Encoder
Not for motor type: -
Min
-
Description:
Selecting the encoder connection.
Bit field:
Bit
00
01
p0421[0...n]
Absolute encoder rotary multiturn resolution / Enc abs multiturn
VECTOR_G, ENC
Can be changed: C2(4)
Data type: Unsigned32
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Sets the number of rotations that can be resolved for a rotary absolute encoder.
Notice:
This parameter is automatically preassigned for encoders from the encoder list and for identify encoder (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
170
Signal name
SUB-D
Terminal
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
18
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
18
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
4294967295
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 4010, 4704
Unit selection: -
Expert list: 1
Factory setting
11
Access level: 3
Func. diagram: 4704, 4710
Unit selection: -
Expert list: 1
Factory setting
9
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 bin
0 signal
No
No
Access level: 3
Func. diagram: 4704
Unit selection: -
Expert list: 1
Factory setting
4096
SINAMICS G130/G150