2 Parameters
2.2 List of parameters
p7036[0...n]
Par_circuit circulating current control proportional gain / Circ_I Kp
VECTOR_G (Parallel) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
0.00000 [ohm]
Description:
Sets the proportional gain for the circulating current controller.
The parameter is pre-set to the cable resistance.
p7037[0...n]
Par_circuit circulating current control integral time / I_circ Tn
VECTOR_G (Parallel) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
2.0
Description:
Sets the integral time of the circulating current controller.
The parameter is referred to the current controller sampling time (p0115[0]).
Dependency:
Refer to: p0115
Note:
Using p7037 = 1000, the integral component is deactivated (held in operation). This is the preferred setting for
operation with separate motor winding system.
p7038[0...n]
Par_circuit circulating current control limit / I_circ limit
VECTOR_G (Parallel) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
1 [%]
Description:
Sets the limit of the circulating current controller output values.
The parameter is, depending on the phase, referred to the valve lockout times (p1828, p1829, p1830).
p7040[0...n]
Par_circuit correction valve lockout time phase U / Comp t_lockout U
VECTOR_G (Parallel) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
-1000000.00 [µs]
Description:
For the particular Motor Module, the correction time must be added to the valve lockout time to be compensated for
phase U (p1828).
The corrective value is used to compensate variations/spread in the valve lockout times of Motor Modules for a
parallel circuit configuration.
Dependency:
Refer to: p1828
756
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
200.00000 [ohm]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1000.0
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100 [%]
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
1000000.00 [µs]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00000 [ohm]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
4.0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
50 [%]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [µs]
SINAMICS G130/G150