2 Parameters
2.2 List of parameters
p1160[0...n]
CI: Speed controller speed setpoint 2 / n_ctrl n_set 2
VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for speed setpoint 2 of the speed controller.
Dependency:
Refer to: p1155, r1170
Note:
For OFF1/OFF3, the ramp-function generator ramp is effective.
The ramp-function generator is set (SERVO: to the actual value, VECTOR: To the setpoint (r1170)) and stops the
drive corresponding to the ramp-downtime (p1121 or p1135). While stopping via the ramp-function generator,
STW1.4 is effective (enable ramp-function generator).
When the function module "position control" (r0108.3 = 1) is activated, this connector input is interconnected as
follows as standard:
CI: p1160 = r2562
r1169
CO: Speed controller speed setpoints 1 and 2 / n_ctrl n_set 1/2
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
- [rpm]
Description:
Displays the speed setpoint after the addition of the speed setpoint 1 (p1155) and speed setpoint 2 (p1160).
Dependency:
Refer to: p1155, p1160
Note:
The value is only correctly displayed at r0899.2 = 1 (operation enabled).
r1170
CO: Speed controller setpoint sum / n_ctrl setp sum
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
- [rpm]
Description:
Display and connector output for the speed setpoint after selecting the ramp-function generator.
The value is the sum of speed setpoint 1 (p1155) and speed setpoint 2 (p1160).
Dependency:
Refer to: r1150, p1155, p1160
p1189[0...n]
Speed setpoint configuration / n_ctrl config
VECTOR_G
Can be changed: U, T
Data type: Unsigned16
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the configuration for the speed setpoint.
Bit field:
Bit
00
01
332
Signal name
Interpolation ramp-fct gen/speed controller
active
Interpol. op-loop ctrl /speed controller active Yes
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: p2000
Max
-
Calculated: -
Dyn. index: -
Unit group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: -
Unit group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
-
1 signal
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 3001, 3080
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 3080
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 3
Func. diagram: 3001, 3080,
6300
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 2
Func. diagram: 3080
Unit selection: -
Expert list: 1
Factory setting
0011 bin
0 signal
No
No
SINAMICS G130/G150
FP
3080
3080