p3881
ESM setpoint source / ESM setp_src
VECTOR_G
Can be changed: T
Data type: Integer16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the setpoint source for essential service mode (ESM).
Value:
0:
1:
3:
5:
6:
7:
Note:
ESM: Essential Service Mode
When the essential service mode is activated, the effective speed setpoint is displayed in r1114.
For p3881 = 0:
The last known setpoint value is only transmitted safely if it was present consistently for at least 30 s prior to
activating the essential service mode. If this condition is not met, fixed speed setpoint 15 (p1015) is used.
Speed setpoints from the jog mode (p1058, p1059) are not taken into account.
For p3881 = 5:
The signal source for the setpoint via analog input for TB30/TM31 is set via p3886.
For p3881 = 6:
n_act = 0: pulse suppression and switching-on inhibited.
n_active > 0: braking along the ramp-function generator down ramp (p1121), pulse cancellation and switching-on
inhibited.
For p3881 = 7:
n_act = 0: pulse suppression and switching-on inhibited.
n_act > 0: immediate pulse cancellation and switching-on inhibited.
p3882
ESM setpoint source alternative / ESM setp_src alt
VECTOR_G
Can be changed: T
Data type: Integer16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the alternative setpoint source for essential service mode (ESM).
This setpoint is used when the setpoint source set in p3881 is lost.
Value:
0:
1:
2:
Dependency:
Refer to: p3881
Note:
ESM: Essential Service Mode
The alternative setpoint source is only active for p3881 = 3, 5.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Last known setpoint (r1078 smoothed)
Fixed speed setpoint 15 (p1015)
Fieldbus
TB30/TM31 analog input
Enable the response OFF1
Enable the response OFF2
Last known setpoint (r1078 smoothed)
Fixed speed setpoint 15 (p1015)
Maximum speed (p1082)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
7
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 7033
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 7033
Unit selection: -
Expert list: 1
Factory setting
0
631