2 Parameters
2.2 List of parameters
p0009 = 114: Change component number
This state allows the component number of existing components to be changed using p9914 after the device has
been commissioned for the first time.
p0009 = 115: Parameter download
This state allows the complete device and drive commissioning using the parameter services.
p0009 = 117: Delete component
This state allows components to be deleted using p9917 after the device has been commissioned for the first time.
p0010
Drive commissioning parameter filter / Drv comm. par_filt
VECTOR_G
Can be changed: C2(1), T
Data type: Integer16
P-Group: All groups
Not for motor type: -
Min
0
Description:
Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value:
0:
1:
2:
3:
4:
5:
15:
17:
25:
29:
30:
95:
10000: Ready with immediate feedback signal
Notice:
For p0010 = 10000 the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
The drive can only be switched on outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
p0010 = 10000 corresponds to p0010 = 0. Unlike with p0010 = 0, the parameter modification is applied immediately
and the calculations are made in the background. Further parameter modifications cannot be made while the
calculations are being performed.
p0010
Infeed commissioning parameter filter / INF comm par_filt
B_INF
Can be changed: C2(1), T
Data type: Integer16
P-Group: All groups
Not for motor type: -
Min
0
Description:
Sets the parameter filter to commission an infeed unit.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value:
0:
1:
2:
5:
29:
30:
42
Ready
Quick commissioning
Power unit commissioning
Motor commissioning
Encoder commissioning
Technological application/units
Data sets
Basic positioner commissioning
Position control commissioning
Only Siemens int
Parameter reset
Safety Integrated commissioning
Ready
Quick commissioning
Power unit commissioning
Technological application/units
Only Siemens int
Parameter reset
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
30
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: 2800, 2818
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS G130/G150