Example:
In order that for a Quick Stop (OFF3) the fixed torque limit is effective, binector input: p1551 must be interconnected
to r0899.5.
p1552[0...n]
CI: Torque limit upper scaling without offset / M_max up w/o offs
VECTOR_G (n/M)
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Sets the signal source for the scaling of the upper torque limiting to limit the speed controller output without taking
into account the current and power limits.
p1553[0...n]
Stall limit scaling / Stall limit scal
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: SESM, REL
Min
80.0 [%]
Description:
Sets the scaling of the stall limit for the start of field weakening.
Danger:
If the stall current limit is increased, then the q current setpoint can exceed the stall limit; as a consequence, a
hysteresis effect can occur when loading and unloading.
p1554[0...n]
CI: Torque limit lower scaling without offset / M_max low w/o offs
VECTOR_G (n/M)
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Sets the signal source for the scaling of the lower torque limiting to limit the speed controller output without taking into
account the current and power limits.
p1555[0...n]
CI: Power limit / P_max
VECTOR_G (n/M)
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Sets the signal source for the motoring and negative regenerative power limit.
Dependency:
Refer to: p1530, p1531
Note:
The resulting motoring power limit is the minimum from p1530 and the signal which is read in.
The resulting regenerative power limit is the maximum from p1531 and the negative signal which is read in.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
130.0 [%]
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: r2004
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6060
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]
Access level: 3
Func. diagram: 6060
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 6640
Unit selection: -
Expert list: 1
Factory setting
1