Siemens G130 List Manual page 261

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p0776[0...2]
Test socket mode / Test skt mode
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: Terminals
CU_G150_DP
Not for motor type: -
Min
96
Description:
Sets the mode for the test sockets.
Value:
96:
97:
98:
99:
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Refer to: p0771, r0772, r0774, p0777, p0778, p0779, p0780, p0783, p0784, r0786, p0788, p0789, r0790
p0777[0...2]
Test socket characteristic value x1 / Test skt char x1
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Terminals
CU_G150_DP
Not for motor type: -
Min
-100000.00 [%]
Description:
The scaling characteristic for the test sockets is defined using two points.
This parameter specifies the x coordinate (percentage) of the first point on the characteristic.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Can only be set when p0776 = 99.
Refer to: p0778, p0779, p0780, r0786
Note:
The value 0.00 % corresponds to 2.49 V.
p0778[0...2]
Test socket characteristic value y1 / Test skt char y1
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Terminals
CU_G150_DP
Not for motor type: -
Min
0.00 [V]
Description:
The scaling characteristic for the test sockets is defined using two points.
This parameter specifies the y coordinate (output voltage) of the first point on the characteristic.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Can only be set when p0776 = 99.
Refer to: p0777, p0779, p0780, r0786
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Physical address (32-bit integer signal unsigned)
Physical address (32-bit integer signal)
Physical address (32-bit floating-point signal)
BICO signal
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
99
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100000.00 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
4.98 [V]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: 8134
Unit selection: -
Expert list: 1
Factory setting
99
Access level: 2
Func. diagram: 8134
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
Access level: 2
Func. diagram: 8134
Unit selection: -
Expert list: 1
Factory setting
2.49 [V]