For p1210 = 4:
An automatic restart is only carried out if fault F30003 occurred at the Motor Module or a 1 signal is present at
binector input p1208[1]. If additional faults are present, then these faults are also acknowledged and when
successful, starting continues. If the 24 V Control Unit power supply fails, then this is interpreted as a line supply
failure.
For p1210 = 6:
An automatic restart is carried out if any fault has occurred or there is a 1 signal at binector input p1208[0].
For p1210 = 14:
as for p1210 = 4. However, active faults must be manually acknowledged.
For p1210 = 16:
as for p1210 = 6. However, active faults must be manually acknowledged.
p1210
Automatic restart mode / AR mode
B_INF
Can be changed: U, T
Data type: Integer16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the automatic restart mode (AR).
Value:
0:
1:
6:
Dependency:
The automatic restart requires an active ON command (e.g., via a digital input). If, for p1210 > 1, there is no active
ON command, then the automatic restart is interrupted.
When using an Advanced Operator Panel (AOP) in the LOCAL Mode, then there is no automatic restart.
Refer to: p0840, p0857, p1267
Refer to: F30003
Danger:
If the automatic restart is activated (p1210 > 1) if there is an ON command (refer to p0840), the drive is switched on
as soon as any fault messages that are present can be acknowledged. This also occurs after the line supply returns
or the Control Unit boots if the DC link voltage is again present or the feedback of the line supply infeed (refer to
p0864) is again available. This automatic switching-on operation can only be interrupted by withdrawing the ON
command.
Notice:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
For p1210 > 1, the infeed is automatically started.
Note:
For p1210 = 1:
Faults that are present are automatically acknowledged. If new faults occur after a successful fault acknowledgment,
then these are also automatically acknowledged again. A minimum time of p1212 + 1 s must expire between a
successful fault acknowledgment and a fault re-occurring if the signal ON/OFF1 (STW1.0) is at a HIGH signal level. If
the signal ON/OFF1 is at a LOW signal level, then the time between a successful fault acknowledgment and a new
fault must be at least 1 s. p1211 has no influence on the number of acknowledgment attempts.
For p1210 = 6:
An automatic restart is carried out if any fault has occurred.
p1211
Automatic restart start attempts / AR start attempts
VECTOR_G
Can be changed: U, T
Data type: Unsigned16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the start attempts of the automatic restart function for p1210 = 4, 6.
Dependency:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Refer to: p1210, r1214
Refer to: F07320
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Inhibit automatic restart
Acknowledge all faults without restarting
Restart after fault with additional start attempts
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
6
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
3
339