Siemens G130 List Manual page 148

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0358[0...n]
Motor rotor leakage inductance / damping inductance d axis / Mot L_r leak / LDd
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PMSM, REL, RESM
Min
0.00000 [mH]
Description:
Sets the rotor/secondary section leakage inductance of the motor.
For separately excited synchronous motors: Sets the damping inductance in the rotor direction (d-axis).
This value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification routine
(p1910) (not for separately excited synchronous motors).
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
VECTOR:
If the rotor leakage inductance (p0358) for induction motors is changed outside the commissioning phase (p0010 >
0), then the magnetizing inductance (p0360) is automatically adapted to the new EMF (r0337). You are then advised
to repeat the measurement for the saturation characteristic (p1960).
p0359[0...n]
Motor damping inductance q axis / Mot L_damp q
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, PMSM, REL,
RESM
Min
0.00000 [mH]
Description:
Sets the damping inductance of the separately excited synchronous motor quadrature to the rotor direction (q axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2).
p0360[0...n]
Motor magnetizing inductance/magn. inductance d axis saturated / Mot Lh/Lh d sat
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PMSM, REL, RESM
Min
0.00000 [mH]
Description:
Sets the magnetizing inductance of the motor.
For separately excited synchronous motors: Sets the saturated magnetizing inductance in the rotor direction (d-axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor
identification routine (p1910) (not for separately excited synchronous motors).
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
148
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Unit group: 15_1
Scaling: -
Max
1000.00000 [mH]
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Unit group: 15_1
Scaling: -
Max
1000.00000 [mH]
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Unit group: 15_1
Scaling: -
Max
10000.00000 [mH]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 6727
Unit selection: p0349
Expert list: 1
Factory setting
0.00000 [mH]
Access level: 3
Func. diagram: 6727
Unit selection: p0349
Expert list: 1
Factory setting
0.00000 [mH]
Access level: 3
Func. diagram: 6727
Unit selection: p0349
Expert list: 1
Factory setting
0.00000 [mH]