2 Parameters
2.2 List of parameters
r1258
CO: Vdc controller output / Vdc_ctrl output
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: REL
Min
- [Arms]
Description:
Displays the actual output of the Vdc controller (DC link voltage controller)
Note:
The regenerative power limit p1531 is used for vector control to pre-control the Vdc_max controller. The lower the
power limit is set, the lower the correction signals of the controller when the voltage limit is reached.
p1260
Bypass configuration / Bypass config
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Integer16
P-Group: -
Not for motor type: RESM
Min
0
Description:
Sets the configuration for the bypass function.
Value:
0:
1:
2:
3:
Note:
If the bypass function is selected ((p1260 > 0), then when the power unit restarts after POWER OFF, the state of the
bypass switch is evaluated. This means that after the ramp-up, it is possible to directly change into the standby
mode. This is only possible for p1267 = 1 (bypass using the control signal) and if the control command after the
system has been booted is still available (p1266). This function has a higher priority than the automatic restart
function (p1210).
The "bypass" function can only be switched off again (p1260 = 0) if the bypass is not active or the bypass function
has a fault.
The corresponding function should be activated in p3800 for bypass with synchronization.
r1261.0...11
CO/BO: Bypass control/status word / Bypass STW / ZSW
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: Unsigned32
P-Group: -
Not for motor type: RESM
Min
-
Description:
Control and feedback signals of the bypass switch.
Bit field:
Bit
00
01
02
03
05
06
07
08
09
10
11
Dependency:
Refer to: p2369
Note:
Control bits 0 and 1 should be interconnected to the signal outputs via which the switches in the motor feeder cables
should be controlled. These should be selected/dimensioned for switching under load.
360
Bypass deactivated
Bypass with synchronization and overlap
Bypass with synchronization without overlap
Bypass without synchronization
Signal name
Command switch motor - power unit
Command switch motor - line supply
Synchronization requested
Staging status
Feedback signal switch motor - power unit
Feedback signal switch motor - line supply
Bypass command (from p1266)
Feedback signal synchronization completed
(from p1268)
Staging requested (from p2369)
Bypass in process sequence
Bypass enabled
Calculated: -
Dyn. index: -
Unit group: 6_2
Scaling: p2002
Max
- [Arms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Close
Close
Yes
Active
Closed
Closed
Yes
Yes
Yes
Yes
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 6220
Unit selection: p0505
Expert list: 1
Factory setting
- [Arms]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Open
Open
No
Not active
Opened
Opened
No
No
No
No
No
SINAMICS G130/G150