Siemens G130 List Manual page 834

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p8790
CAN control word - auto interconnection / STW interc auto
VECTOR_G (CAN)
Can be changed: C1(3), T
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Sets the automatic BICO interconnection of the CANopen control word.
Value:
0:
1:
Dependency:
Refer to: r2050, r2090, r2091, r2092, r2093, r8750, r8795, r8850, r8890, r8891, r8892, r8893
Note:
The following BICO interconnections are automatically established if the CANopen control word is mapped at one of
the locations x = 0 ... 3 in the receive process data buffer.
For SINAMICS S120 with CBC10, the PZD interface IF2 is used:
BI: p0840.0 = r889x.0
BI: p0844.0 = r889x.1
BI: p0848.0 = r889x.2
BI: p0852.0 = r889x.3
BI: p2103.0 = r889x.7
For SINAMICS S110, the PZD interface IF1 is used:
BI: p0840.0 = r209x.0
BI: p0844.0 = r209x.1
BI: p0848.0 = r209x.2
BI: p0852.0 = r209x.3
BI: p2103.0 = r209x.7
The write access is rejected if a CANopen control word is not mapped at one of these locations.
This also causes the project download of the commissioning software to be canceled.
p8791
CAN stop option code / Stop opt_code
VECTOR_G (CAN)
Can be changed: C1(3), T
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
-1
Description:
Setting for the CANopen control word bit 8 "Stop" (CANopen STW.8).
Value:
-1:
1:
3:
Dependency:
Refer to: r8750, r8795, r8850
Note:
Corresponds to the CANopen object 605D hex + 800 hex * x (x: drive number 0 ... 7).
The BICO interconnection is established, if the CANopen control word is mapped at one of the locations x = 0 ... 3 in
the receive process data buffer.
834
No interconn
Interconnection
No interconn
Interconnection CANopen STW.8 with p1142
Interconnection CANopen STW.8 with p1140
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-1