2 Parameters
2.2 List of parameters
p0151[0...1]
DRIVE-CLiQ Hub Module component number / Hub comp_no
HUB
Can be changed: C1(4)
Data type: Unsigned8
P-Group: Data sets
Not for motor type: -
Min
0
Description:
This parameter is used to assign the data set to a DRIVE-CLiQ Hub Module.
This unique component number is assigned when parameterizing the topology.
Only the numbers of components operated as hubs can be entered in these parameters.
[0] = DRIVE-CLiQ node 1
[1] = DRIVE-CLiQ node 2
p0154
Terminal Module detection via LED / TM detection LED
TM31, TM120, TM150,
Can be changed: U, T
TM54F_MA,
Data type: Unsigned8
TM54F_SL
P-Group: Terminals
Not for motor type: -
Min
0
Description:
Detects the Terminal Module assigned to this drive and data set.
Note:
While p0154 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Terminal Module.
p0154
DRIVE-CLiQ Hub Module detection via LED / Hub detection LED
HUB
Can be changed: U, T
Data type: Unsigned8
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Detects any DRIVE-CLiQ Hub Module that has been assigned.
p0155[0...n]
Voltage Sensing Module activate/deactivate / VSM act/deact
VECTOR_G
Can be changed: C1(4), T
Data type: Integer16
P-Group: Data sets
Not for motor type: -
Min
0
Description:
Setting to activate/deactivate a Voltage Sensing Module (VSM).
Value:
0:
1:
2:
Recommendation:
After inserting a component, before activating, first wait for Alarm A01317.
Dependency:
Refer to: r0156
Refer to: A01314, A01317
98
Deactivate component
Activate component
Component deactivate and not present
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
199
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: p0150
Unit group: -
Scaling: -
Max
2
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS G130/G150